Minor amenity features eligible for validation

Retractable awning

The technical specifications of the retractable awning for validation and corresponding minor works items are listed in Part 4 of Schedule 3 of the Building (Minor Works) Regulation (B(MW)R). The works must be in existence or completed before 1 September 2020.

The prescribed building or building works item

17

The prescribed building or building works items 17

Corresponding minor works item

2.43

  1. For an opening on an external wall of a building and the opening is:
    • door opening (other than a door opening that serves as an exit for an escape staircase or that leads to a balcony or verandah); or
    • window opening (other than a window opening for a plant room, lavatory, bathroom or kitchen)
  2. Projecting from an external wall
    • When retracted
      ≤ 500mm
    • When fully extended
      • ≤ 2m (over a roof)
      • ≤ 2.5m (in any other case)
  3. Distance between the highest point of the awning and the roof (if the awning is above a roof) or the ground (in any other case)
    < 5.5m
  4. Not fixed to any cantilevered slab
  5. No part is above the ceiling of the storey on which the opening is located
  6. The awning is at most 500mm wider than the opening on both the left-hand side and the right-hand side of the opening