Minor amenity features eligible for validation

Pole

The technical specifications of the pole for validation and corresponding minor works items are listed in Part 4 of Schedule 3 of the Building (Minor Works) Regulation (B(MW)R). The works must be in existence or completed before 1 September 2020.

Pole on-grade

The prescribed building or building works item

12

The prescribed building or building works items 12

Corresponding minor works item

2.53

  1. Height of the pole, including any feature at its top
    ≤ 5m
  2. Weight of the pole, including any feature at its top but excluding any pedestal
    ≤ 150kg
  3. Not falling within the description of Designated Exempted Works item 17

Pole on a roof of a building

The prescribed building or building works item

13

The prescribed building or building works items 13
The prescribed building or building works items 13

Corresponding minor works items

2.54

  1. Height of the pole, including any feature at its top
    > 1.5m but ≤ 2.5m
  2. Weight of the pole, including any feature at its top but excluding any pedestal
    ≤ 100kg
  3. If there is more than one pole on the roof, the poles are at least 2.5m away from each other
  4. Thickness of the roof slab supporting the pole
    ≥ 150mm
  5. No additional load to any cantilevered slab
  6. Not involving alteration to any other structural elements

3.54

  1. Height of the pole, including any feature at its top
    ≤ 1.5m
  2. Weight of the pole, including any feature at its top but excluding any pedestal
    ≤ 100kg
  3. If there is more than one pole on the roof, the poles are at least 2.5m away from each other
  4. Thickness of the roof slab supporting the pole
    ≥ 150mm
  5. No additional load to any cantilevered slab
  6. Not involving alteration to any other structural elements